Metering real and apparent energy results, Ite to the – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 210

210
Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Metering Real and Apparent Energy Results Parameters
CSP File No.
N20
Remote I/O BT
29
CIP Assy. Inst.
19 (Write), 20 (Read)
No. of Elements
23
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Metering Real and Apparent Energy Results
Element
No.
Modbus
Address
Element Name
Range
Units
Default
Value
Comment
0
40501
Password
0…9999
-
0
Required to clear or preset energy counters.
Returns -1.
1
40502
Parameter select
0 to 7
(bitfield)
-
Refer to How to Clear or Preset Energy
Counters by Using Communication on
page 120
.
2
40503
kWh forward
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999
kWh
3
40504
4
40505
5
40506
6
40507
7
40508
kWh reverse
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999
8
40509
9
40510
10
40511
11
40512
12
40513
kWh net
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999…999
13
40514
14
40515
15
40516
16
40517
17
40518
kVAh
### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10-
3
-999…999
KVAh
18
40519
19
40520
20
40521
21
40522
22
40523
Metering iteration
0…32,767
-
Increments by 1…32,767, rolls over to 0.