Class code 0xf0 — controlnet object, Class attributes instances instance attributes – Rockwell Automation 1203-CN1 ControlNet Communications Module 1203-CN1 User Manual

Page 107

Advertising
background image

Publication 1203-5.13 – February, 2002

ControlNet Objects: Class Code 0xF0 — ControlNet Object

D-21

Class Code 0xF0 — ControlNet
Object

The ControlNet Object provides a consistent Station Management
interface to the Physical and Data Link Layers. This object makes
diagnostic information from these layers available to client
applications.

Class Attributes

Instances

Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Description

0x01

Get

Revision

UINT

Revision of this object. First revision,
value=1.

0x02

Get

Max Instance

UDINT

Maximum instance number. Value
determined by node specifics.

Instance

Description

1

ControlNet Status

Attribute ID

Access Rule

Name

Data Type

Description

0x81

Get

current_link_config

STRUCT of 34

BYTEs

Current link configuration parameters.

0x82

Get/Get_and_

Clear

diagnostic_counters STRUCT of 42

BYTEs

Diagnostic counters.

buffer_errors

UINT

Buffer event counters.

error_log

BYTE [8]

Bad MAC frame log.

event_counters

STRUCT of 32

BYTEs

Diagnostic counters.

good_frames_
transmitted

BYTE [3]

Good MAC frames transmitted (LSB
first).

good_frames_
received

BYTE [3]

Good MAC frames received (LSB first).

selected_channel_
frame_errors

USINT

Framing errors detected on active
receive channel.

channel_A_frame_
errors

USINT

Framing errors detected on active
receive channel.

channel_B_frame_
errors

USINT

MAC frames aborted during
transmission (transmit underflows).

aborted_frames_
transmitted

USINT

MAC frames aborted during
transmission (transmit underflows).

highwaters

USINT

LLC transmit underflow and LLC
receive overflow.

Advertising