Rockwell Automation 1203-CN1 ControlNet Communications Module 1203-CN1 User Manual

Page 92

Advertising
background image

Publication 1203-5.13 – February, 2002

D-6

ControlNet Objects: Class Code 0x02 — Message Router Object

Instance Attributes

Common Services

Get_Attribute_All Response

At the class level, the order of the attributes returned in the
Get_Attribute_All response is as follows:

At the instance level, the order of attributes returned in the
Get_Attribute_All response is as follows:

Attribute ID

Access Rule

Name

Data Type

Description

1

Get

Object_List

STRUCT of

A list of supported objects.
Structure with an array of object class codes
supported by the device via the message router.

Number

UINT

Number of supported classes in the classes
array.

Classes

ARRAY of

UINT

List of supported class codes.

2

Get

Number available

UINT

Maximum number of connections supported.

3

Get

Number active

UINT

Number of connections currently used by
system components.
Not used. Reserved for compatibility purposes.
Value = 0

4

Get

Active connections

ARRAY of

UINT

A list of the connection IDs of the currently
active connections. This attribute not used.
Reserved for compatibility purposes.

Service Code

Implemented for:

Service Name

Class

Instance

0x01

Yes

Yes

Get_Attribute_All

0x0E

Yes

Yes

Get_Attribute_Single

Class Attribute ID

Definition

1

Revision Default = 1

4

Optional attribute list, number of attributes default = 0

5

Optional service list, number of services default = 0

6

Max ID number of class attributes default = 0

7

Max ID number of instance attributes default = 0

Instance Attribute ID

Definition

1

Object list number, number of supported classes default = 0

2

Number available, maximum number of connections default = 0

3

Always = 0x000

Advertising