Pccc error response codes, Related documentation – Rockwell Automation 1203-CN1 ControlNet Communications Module 1203-CN1 User Manual

Page 118

Advertising
background image

Publication 1203-5.13 – February, 2002

E-2

Supported PCCC Messages

PCCC Error Response Codes

The following table lists the PCCC error response codes.

Related documentation

For more information on PCCC messages, refer to the DF1 Protocol
and Command Set Reference Manual, publication 1770-6.5.16.

Messages

STS

EXT STS

Problem

All Messages

0x10

Illegal command or format. The adapter does not
support this command.

0x30

Remote station host is not present, disconnected,
or shutdown. The SCANport product is discon-
nected or cannot communicate for some other
reason.

All Messages

where

CMD=0x0F

0xF0

0x01

Illegal Address Format. A field has an illegal value
in a logical binary system address.

0xF0

0x02

Illegal Address Format. Not enough fields speci-
fied in a logical binary system address.

0xF0

0x03

Illegal Address Format. Too many fields specified
in a logical binary system address.

0xF0

0x06

Illegal Address. Address does not exist, or does
not point to something usable by this command.

0xF0

0x0A

Request is too large. Transaction size plus word
address is too large. For example, a write of 10
elements to N50:248 would attempt to write data
beyond the end of the file.

0xF0

0x10

No Access. For example, your message tried to
write to a read-only location.

0xF0

0x11

Illegal data type information. For example, an
attempt to write floating point data to a numeric
[integer] file.

Advertising