ControlNet Objects: Class Code 0x06 — Connection Manager Object

Common Services

9

Get

Connection Entry
List

STRUCT of

List of connections

NumConnEntries

UINT

Number of Conn Array Entries (bit field).
This attribute, divided by 8 and
incremented for any remainder, gives
the length of the array in the Conn Open
Bits field.

ConnOpenBits

ARRAY of

BYTE

List of connection data which may be
individually queried by the Get/Search
Connection Data Services. Each bit
represents a possible connection.
0 = No Connection
1 = Connection Established
Query for more information

11

Get

CpuUtilization

UINT

CPU Utilization in tenths of a percent.
Range of 0 – 1000 representing 0 to
100%.

12

Get

MaxBuffSize

UDINT

Amount of buffer space originally
available. Size is in BYTEs.

13

Get

BufSize Remaining

UDINT

Amount of buffer space available at this
time. Size is in BYTEs.

Important: Instance attribute number 10 is not used.

Attribute ID

Access Rule

Name

Data Type

Description

Service Code

Implemented for:

Service Name

Class

Instance

0x01

Yes

Yes

Get_Attribute_All

0x02

No

Yes

Set_Attribute_All

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single