Common services – Rockwell Automation 1203-CN1 ControlNet Communications Module 1203-CN1 User Manual
Page 96

Publication 1203-5.13 – February, 2002
D-10
ControlNet Objects: Class Code 0x06 — Connection Manager Object
Common Services
9
Get
Connection Entry
List
STRUCT of
List of connections
NumConnEntries
UINT
Number of Conn Array Entries (bit field).
This attribute, divided by 8 and
incremented for any remainder, gives
the length of the array in the Conn Open
Bits field.
ConnOpenBits
ARRAY of
BYTE
List of connection data which may be
individually queried by the Get/Search
Connection Data Services. Each bit
represents a possible connection.
0 = No Connection
1 = Connection Established
Query for more information
11
Get
CpuUtilization
UINT
CPU Utilization in tenths of a percent.
Range of 0 – 1000 representing 0 to
100%.
12
Get
MaxBuffSize
UDINT
Amount of buffer space originally
available. Size is in BYTEs.
13
Get
BufSize Remaining
UDINT
Amount of buffer space available at this
time. Size is in BYTEs.
Important: Instance attribute number 10 is not used.
Attribute ID
Access Rule
Name
Data Type
Description
Service Code
Implemented for:
Service Name
Class
Instance
0x01
Yes
Yes
Get_Attribute_All
0x02
No
Yes
Set_Attribute_All
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single