The portion of the program shown in Figure 5.4 displays the status of
the drive by reading the status information in the drive’s logic status
word and displaying it at the operator’s station.

Figure 5.4
Drive Status Display logic

The portion of the program shown in Figure 5.5 moves a Frequency
Reference to the drive. The word is scaled 0 to 32767 equals 0 to
maximum frequency. Scaling may differ for other products.

Figure 5.5
Drive Frequency Reference

The portion of the program shown in Figure 5.6 moves the drive’s
Frequency Feedback from the drive’s feedback word to the PLC. The
word is scaled 0 to 32767 equals 0 to maximum frequency. This
scaling may differ on other SCANport products.

Figure 5.6

Drive Frequency Feedback Display

Status Display Logic

0003

N12:0

0

Drive
ENABLED
Status
Bit

O:000

0

Operator
Drive Enabled
Status
Display

0004

N12:0

1

Drive
RUNNING
Status
Bit

O:000

1

Operator
Drive Running
Status
Display

0005

N12:0

7

Drive
FAULTED
Status
Bit

O:000

2

Operator
Drive Faulted
Status
Display

Frequency Reference

This rung moves a frequency reference from N7:0 to the drive's FREQUENCY REFERENCE input word at N13:1.

Frequency scaling on the 1305 AC Drive is such that 0 - 32767 = zero - max frequency.

0006

MOV

Move
Source

N7:0

16383<
Dest

N13:1

16383<

MOV

Frequency Feedback

This rung moves the drive's FREQUENCY FEEDBACK from the drive's feedback word at N12:1 to N7:1.

Frequency feedback scaling on the 1305 AC drive is such that 0 - 32767 = zero to max frequency.

0007

MOV

Move
Source

N12:1

0<
Dest

N7:1

0<

MOV

0008

END