Example fault queue read emulated block transfer – Rockwell Automation 1203-CN1 ControlNet Communications Module 1203-CN1 User Manual

Page 72

Advertising
background image

Publication 1203-5.13 – February, 2002

6-6

Using Messages

Example Fault Queue Read Emulated Block Transfer

Figure 6.8 contains an example of an emulated block transfer. In
emulated block transfers, the first rung always writes the data from
the drive to the N:40 file in the module; the second rung then reads
the data from this file.

Important: You can activate only one emulated block transfer
message at a time. If more than one message is active, data may be
processed out of order and inaccurate results may be supplied.

Figure 6.8
Read Fault Queue Entry #1 Logic

The MSG dialog box in Figure 6.9 specifies the configuration for the
Write Probe message. Note the following:

In the Data Table Address field in the This PLC-5 section,
N22:0 is specified. This is where the results will be reported.

In the Size in Elements field in the This PLC-5 section, 10 is
specified. The response will be 10 elements.

In the Data Table Address field in the Target Device section,
N40:0 is specified. This is the location where the fault queue data
will be stored.

Important: If you refer to Appendix C, N-File Structure, you will
find that block transfer emulation data is contained in N40:0 –
N40:63.

Block Transfer Emulation

This rung sends a message that instructs the 1203-CN1 what information to gather from the 1305 AC Drive. The message can be 3 to
64 words long.

0002

I:000

17

User
Input

EN

DN

ER

MSG

Read/Write Message
Control

MG15:2

Setup Screen

MSG

When the previous MSG instruction completes, this rung reads the information requested from the 1203-CN1. The response message
can be 3 to 64 words long.

0003

MG15:2

DN

Write Probe
Message
Completed

EN

DN

ER

MSG

Read/Write Message
Control

MG15:3

Setup Screen

MSG

0004

END