Getting Started

3-13

3. Scroll through the list of DF1 statistic parameters by pressing the

Up Arrow or Down Arrow key.

4. If desired, reset the current DF1 protocol statistics by setting

Clear DF1 Counts to Enable and pressing the Enter key.

5. Press the Escape key to return to the main menu.

Viewing Your 1203-CN1 Module’s
Serial Number

Each 1203-CN1 module has a unique serial number. To view the
serial number, follow these instructions:

1. Establish a serial connection to access the module’s software.

Refer to the Establishing a Serial Connection with the 1203-CN1
Module
section earlier in this chapter.

2. Press 6 to select 6> Display serial number. The serial number

for your communications module appears.

3. Press Escape to return to the Main Menu.

Number

Name

Description

1

Clear DF1 Counts

Ready = Accept default
Enable = Reset all status parameters

2

DF1 Packets Sent

Total number of DF1 packets sent by the module

3

DF1 Packets Rcvd

Total number of DF1 packets received by the module

4

Undelivered Msgs

Total number of messages sent that were not acknowledged

5

ENQ Sent

Total number of inquiries sent by the module

6

ENQ Rcvd

Total number of inquiries received by the module

7

NAKs Received

Total number of NAKs received by the module

8

NAK Bad Packet

Total number of NAKs received by the module

9

NAK No Memory

Total number of NAKs sent by the module because the previous
command did not yet complete and there was no place to save the new
command

10

Duplicate Msgs

Total number of messages received by the module with the TNS number