Application Does Not Run

If a compact application does not run on the terminal, there may be a
problem with the FactoryTalk View ME application. Verify that a
startup screen was configured and that the runtime file is a compatible
version.

Configuration Mode Access

To access Configuration mode while an application is running, your
FactoryTalk View ME application must contain a screen with a Goto
Configure Mode button. When the application is running, you can
press this button to access Configuration mode.

If a running application does not contain a Goto Configure Mode
button, you can access configuration mode during startup.

1. Restart the terminal.

The terminal goes through its startup sequence and will display
a white box in the lower left corner of the display.

2. On touch screen terminals, press the white box.

On keypad terminals, press the F1 key.

The terminal enters Configuration Mode.

TIP

If the terminal is configured to enter Configuration mode at
startup and does not, then reload the firmware.