Mount the 400 or 600
Terminal in a Panel

Mounting levers secure the terminal to the panel. The number of
levers you use (4 or 6) varies by terminal type.

Follow these steps to mount the 400 or 600 terminals in a panel.

1. Cut an opening in the panel by using the panel cutout shipped

with the terminal.

2. Make sure the terminal sealing gasket is properly positioned on

the terminal.

This gasket forms a compression-type seal. Do not use sealing
compounds.

3. Place the terminal in the panel cutout.

If installing the terminal in an existing 550 panel cutout, align
the terminal with the center of the cutout for best gasket sealing.

4. Insert all mounting levers into the mounting slots on the

terminal.

ATTENTION

Disconnect all electrical power from the panel before making
the panel cutout.

Make sure the area around the panel cutout is clear.

Take precautions so metal cuttings do not enter any
components already installed in the panel.

Failure to follow these warnings may result in personal injury or
damage to panel components.

Sealing Gasket