Publication 2711PC-UM001A-EN-P - March 2009

Chapter 6 Terminal Connections

PanelView Plus Compact to Logix Controllers

PanelView Plus Compact to Logix Communication Adapters

Communication Port
Isolation

The table summarizes electrical isolation for the communication ports
on the PanelView Plus Compact terminals.

Cables: PanelView Plus Compact to Logix Controllers

Protocol

PanelView Plus Compact

400, 600, 1000 Comm Port

ControlLogix

CH0 (9-pin RS-232)

(DF1)

CompactLogix

CH0 (9-pin RS-232)

(DF1 or DH-485)

DF1

RS-232 (DF1) Comm port (9-pin)

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

DH-485

RS-232 (DH-485) Comm port (9-pin)

N/A

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

EtherNet/IP

EtherNet/IP Comm port

Use 1756-ENET or 1756-ENBT module

with Ethernet cable

To 1769-L35E with Ethernet cable

Cables: PanelView Plus Compact to Communication

Adapters

Protocol

PanelView Plus Compact

400, 600, 1000 Comm Port

1761-NET-AIC

Port 1 (9-pin)

Port 2

8-pin Mini DIN

Port 3

(DH-485)

DF1

RS-232 Comm port (9-pin)

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft)

N/A

DH-485

RS-232 Comm port (9-pin)

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft)

N/A

Communication Port

400 and 600 Terminal

1000 Terminal

RS-232

Nonisolated

Isolated

USB

Nonisolated

Nonisolated

Ethernet

Isolated

Isolated