Installing the Terminal

Chapter Objectives

This chapter provides pre-installation information and procedures on
how to install the terminals.

Hazardous locations

Environment and enclosure

Required tools

Clearances

Panel cutout dimensions

Mount the 400 or 600 terminal in a panel

Mount the 1000 terminal in a panel

Product dimensions

Hazardous Locations

This equipment is suitable for these locations:

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups F, G

Class III

ordinary, nonhazardous locations

The following statement applies to use in hazardous locations.

The terminals have a temperature code of T4 when operating in a
55 °C (131 °F) maximum ambient temperature. Do not install the
terminals in environments where atmospheric gases have ignition
temperatures less than 135 °C (275 °F).

WARNING

Explosion Hazard

Substitution of components may impair suitability for hazardous
locations.

Do not disconnect equipment unless power has been switched off
and area is known to be nonhazardous.

Do not connect or disconnect components unless power has been
switched off.

All wiring must comply with N.E.C. articles 501, 502, 503, and/or
C.E.C. section 18-1J2 as appropriate.

Peripheral equipment must be suitable for the location in which it is