Installing the Terminal Chapter 2
Required Tools
These tools are required for panel installation:
•
Panel cutout tools
•
Small, slotted screwdriver
•
Torque wrench (lb•in) for tightening the mounting clips on the
1000 terminal
Clearances
Allow adequate clearance around the terminal, inside the enclosure,
for adequate ventilation. Consider heat produced by other devices in
the enclosure. The ambient temperature around the terminals must be
between 0…55 °C (32…131 ºF).
Cutout Dimensions
Use the full size template shipped with your terminal to mark the
cutout dimensions.
Clearance Area 400 and 600 Terminals
1000 Terminal
Top
51 mm (2 in.)
51 mm (2 in.)
Bottom
102 mm (4 in.)
51 mm (2 in.)
Side
(1)
(1)
Minimum side clearance for insertion of memory card and cable wiring is 102 mm (4 in.).
25 mm (1 in.)
25 mm (1 in.)
Back
None
25 mm (1 in.)
Terminal Type
Height mm (in.)
Width mm (in.)
400 Keypad, or Keypad and Touch
123 (4.86)
156 (6.15)
600 Touch
123 (4.86)
156 (6.15)
1000 Touch
224 (8.8)
305 (12.00)