Installing the Terminal Chapter 2

Required Tools

These tools are required for panel installation:

Panel cutout tools

Small, slotted screwdriver

Torque wrench (lb•in) for tightening the mounting clips on the
1000 terminal

Clearances

Allow adequate clearance around the terminal, inside the enclosure,
for adequate ventilation. Consider heat produced by other devices in
the enclosure. The ambient temperature around the terminals must be
between 0…55 °C (32…131 ºF).

Cutout Dimensions

Use the full size template shipped with your terminal to mark the
cutout dimensions.

Clearance Area 400 and 600 Terminals

1000 Terminal

Top

51 mm (2 in.)

51 mm (2 in.)

Bottom

102 mm (4 in.)

51 mm (2 in.)

Side

(1)

(1)

Minimum side clearance for insertion of memory card and cable wiring is 102 mm (4 in.).

25 mm (1 in.)

25 mm (1 in.)

Back

None

25 mm (1 in.)

Terminal Type

Height mm (in.)

Width mm (in.)

400 Keypad, or Keypad and Touch

123 (4.86)

156 (6.15)

600 Touch

123 (4.86)

156 (6.15)

1000 Touch

224 (8.8)

305 (12.00)