Earth/ground connection – Rockwell Automation 2711PC-xxxx PanelView Plus Compact User Manual User Manual

Page 27

Advertising
background image

Publication 2711PC-UM001A-EN-P - March 2009

27

Connecting Power Chapter 3

Earth/Ground Connection

You must connect the earth/ground terminal to a low-impedance
earth/ground.

The 1000 terminals have the earth/ground connection on the
rear of the display module.

The 400 and 600 terminals have the functional earth/ground
connection on the power input terminal block.

The earth terminal requires a minimum wire gauge.

Earth Wire Specifications

On most PanelView Plus DC terminals, the earth/ground terminal is
internally connected to the DC- terminal within the product.

The PanelView Plus terminals have isolated and nonisolated
communication ports. Refer to

Communication Port Isolation

page

88

for details.

IMPORTANT

The earth/ground connection to ground is mandatory. This
connection is required for noise immunity, reliability, and
Electromagnetic Compliance (EMC) with the European Union
(EU) EMC directive for CE-mark conformance and is required for
safety by Underwriters Laboratory.

Terminal

Symbol

Wire Type

Wire Gauge

Terminal Screw Torque

400 and 600

Stranded or solid

Cu 90 °C (194 °F)

14…12 AWG

0.45…0.56 N•m (4…5 lb•in)

1000

GND

14…10 AWG

1.13…1.36 N•m (10…12 lb•in)

ATTENTION

Damage or malfunction can occur when a voltage potential
exists between two separate ground points. Make sure the
terminal does not serve as a conductive path between ground
points at different potentials.

IMPORTANT

For more information, refer to Wiring and Grounding Guidelines
for PanelView Plus Devices, publication

2711P-TD001

.