Usb ports – Rockwell Automation 2711PC-xxxx PanelView Plus Compact User Manual User Manual

Page 14

Advertising
background image

14

Publication 2711PC-UM001A-EN-P - March 2009

Chapter 2 Installing the Terminal

USB Ports

The PanelView Plus Compact terminals contain universal serial bus
(USB) ports that comply with hazardous location environments. This
section details the field-wiring compliance requirements and is
provided in accordance with the National Electrical Code, article 500.

PanelView Plus Compact Terminals Control Drawing

Selected nonincendive field wiring apparatus must have nonincendive
circuit parameters conforming with Table 2.

Table 1 - PanelView Plus Compact USB Port Circuit Parameters

Display Size

V

oc

I

sc

C

a

L

a

Groups

A and B

Groups

C and D

Groups

A and B

Groups

C and D

400 and 600

Series C or later

5.25V DC 1.68 A

10 µF

10 µF

3.5 µH

15 µH

1000

5.25V DC 1.68 A

10 µF

10 µF

15 µH

15 µH

Table 2 - Required Circuit Parameters for the USB Peripheral Device

V

max

V

oc

I

max

I

sc

C

i

+ C

cable

£ C

a

L

i

+ L

cable

£ L

a

USB

Peripheral

Device

Nonincendive Field
Wiring Apparatus

USB Port

Nonincendive Field Wiring

Associated Nonincendive Field Wiring Apparatus

PanelView Plus 400, 600, or 1000 Host Product

Advertising