6 - terminal connections, Chapter objectives, Cables for runtime communication – Rockwell Automation 2711PC-xxxx PanelView Plus Compact User Manual User Manual

Page 87: Chapter 6, Terminal connections, Chapter

Advertising
background image

87

Publication 2711PC-UM001A-EN-P - March 2009

87

Chapter

6

Terminal Connections

Chapter Objectives

This chapter provides network and device connections for the
terminals.

Runtime communication cables

Communication port isolation

USB ports

Serial connections on base unit

Ethernet (onboard communication)

Cables for Runtime
Communication

The tables provide a summary of terminal connections to controllers
and network interface modules for runtime communication.

PanelView Plus Compact Terminals to MicroLogix Controllers

PanelView Plus Compact Terminals to SLC Controllers

Cables: PanelView Plus Compact Terminals to SLC Controllers

Protocol

PanelView Plus Compact

400, 600, 1000 Comm Port

SLC-500, 5/01, 5/02

CH1 RJ45

(DH-485)

SLC-5/03, 5/04, 5/05

CH0 (9-pin RS-232)

(DF1 or DH-485)

SLC 5/03

CH1 (RJ45)

(DH-485)

SLC 5/04

CH1 (DH+)

SLC 5/05

CH1 (ENET)

DF1

RS-232 (DF1) Comm port (9-pin)

N/A

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

N/A

N/A

N/A

DH-485

RS-232 (DH-485) Comm port (9-pin)

Use AIC+ module

(1761-NET-AIC)

Connect to port 1 or 2

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

Use AIC+ module

(1761-NET-AIC)

Connect to port 1 or 2

N/A

N/A

EtherNet/IP

EtherNet/IP Comm port

N/A

Use 1761-NET-ENI module

with Ethernet cable

N/A

N/A

2711P- CBL-EX04 Ethernet

crossover cable

(1)

(1)

An EtherNet/IP direction connection between a PanelView Plus Compact terminal and an SLC 5/05 requires hub or crossover cable listed.

Cables: PanelView Plus Compact to MicroLogix Controllers

Protocol

PanelView Plus Compact

400, 600, 1000 Comm Port

MicroLogix 1500LRP

CH1 (9-pin RS-232)

(DF1 or DH-485)

MicroLogix 1000, 1200, 1500LSP

CH0 (8-pin Mini DIN)

(DF1 or DH-485)

MicroLogix 1100, 1400

Ethernet Port

DF1

RS-232 (DF1) Comm port (9-pin)

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft)

(null modem not required)

(1)

N/A

DH-485

RS-232 (DH-485) Comm port (9-pin)

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft)

(null modem not required)

(1)

N/A

EtherNet/IP

EtherNet/IP Comm port

Use 1761-NET-ENI module

with Ethernet cable

Ethernet cable

(1)

AIC+ Module recommended for isolation when PanelView and controller are not using same power supply.

Advertising