Computer connections – Rockwell Automation 2711PC-xxxx PanelView Plus Compact User Manual User Manual
Page 92
92
Publication 2711PC-UM001A-EN-P - March 2009
Chapter 6 Terminal Connections
Computer Connections
The RS-232 serial port on the base-configured unit of the terminals
supports:
•
application uploads/downloads using a direct connection.
•
printing.
Available Cables
Cat. No. 2711-NC13, 5 m (16.4 ft)
Cat. No. 2711-NC14, 10 m (32.7 ft)
Cat. No. 2706-NC13, 3 m (10 ft)
25-pin to 9-pin
Adapter (if required)
PanelView Plus Compact Terminals
RS-232 Port
Computer
PanelView Port (DCE)
Computer Port (DTE)
with Handshaking
9-pin male
9-pin male
1 NC
1
DCD
2
2
RXD (Data Receive)
3
3
TXD (Data Transmit)
4 NC
4
5
5
COM
6 (pulled high to +12V)
6
DSR
7
7
RTS
8
8
CTS
9 NC
9
NC
Upload/Download Cable without Hardware Handshaking
PanelView Printer Port
(DCE)
Computer Port
(DTE)
9-pin male
9-pin
25-pin
2
2
3
3
3
2
5
5
7
RXD
TXD
COM
DSR
RTS
CTS
RXD
TXD
COM