Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

15

Shipping and Handling Procedures

Chapter 1

Initial Inspection Checklist

Storage

Store the drive in a dry, clean and cool area.

The storage temperature must be maintained between -25...55 °C. If the storage
temperature fluctuates significantly or if the relative humidity exceeds 90%, use
heating and moisture protection devices to prevent condensation.

Store the drive in a conditioned building with adequate air circulation. Do not
store the drive outdoors.

Installation Site
Requirements

Environmental Conditions

Elevation above sea level must be less than 1000 m (3250 ft)

(1)

.

Ambient air temperature must be between 0...40°C (32...104°F)

(2)

.

Relative humidity must be less than 90%, non-condensing.

The drive must be installed indoors; there must be no dripping water or
other fluids in the room.

Cooling air must be clean without significant concentrations of sand,
corrosive or conductive dust (defined by IEC 721-1 as being less than
0.2 mg/m

of dust), or explosive gas.

Free from significant vibration.

The drive must be anchored on a level floor. Please refer to the dimension
drawing for the anchor point sizes and locations.

For the equipment to operate in conditions other than those specified, consult
the local Rockwell Automation Sales Office.

Table 2 - Shipping Damage Assessment

Bypass Cabinet (if supplied)

Isolation Transformer Cabinet

Power Module Cabinet

Low Voltage Control Cabinet

Low Voltage Door:
❑ Pilot Lights
❑ Voltage Indicator Relay
Cabinet:
❑ Insulators
❑ Switch assemblies
❑ Vacuum contactors
❑ Mechanical linkages

Low Voltage Door:
❑ Transformer Temperature monitor relay
Cabinet:
❑ Voltage Sensing Board
❑ Incoming Line Power Cable Terminal

Insulators

❑ Outgoing Load Power Cable Terminal

Insulators

❑ Transformer Secondary Windings

Inspect nomex wrap
Verify windings from core are

undamaged

Check for debris in top of core

Fixed-mounted:
❑ Power module retaining tabs
Drawout:
❑ Power Module Support frame
❑ Power modules (shipped in separate

crate(s))

Low Voltage Door:
❑ Pilot lights
❑ Push buttons
❑ HMI Interface
Panel:
❑ DIN rail mounted components
❑ UPS
❑ Fiber optic cables
❑ PLC
❑ Control Unit

(1) Options are available for operation up to 3000 m.a.s.l. However, these must be stated at the time of order and cannot be retrofitted

in the field.

(2) Options are available for ambient temperatures up to 50 ºC. However, these must be stated at the time of order and cannot be

retrofitted in the field.