General Wire Categories

General Wire Categories

Conductors
Category

Conductors
Group

Machine With

Signal Examples

Recommended
Cable

Conductors
Group

Power
Supplies
mm (in.)

Control
mm (in.)

To PLC

Power Supplies

1

AC power supply
(TO 600V AC)

220V, 1Ø

Per IEC / NEC,
Local codes and
application
requirements

Tray

228.6 (9.00)

152.4 (6.00)

All signal wiring must be run
in separate steel conduit.

A wire tray is not suitable.

The minimum spacing
between conduits containing
different wire groups is
76.2 mm (3 in.).

Control

2

220V AC or

220V DC Logic

Relay Logic PLC I/O

Per IEC / NEC,
Local codes and
application
requirements

Tray

228.6 (9.00)

152.4 (6.00)

3

24V AC or

24V DC logic

PLC I/O

Per IEC / NEC,
Local codes and
application
requirements

Tray

228.6 (9.00)

152.4 (6.00)

To PLC

4

Analog Signal

DC supply

5...24V DC Supplies

Belden 8760

(1)

Belden 8770

(2)

Belden 9460

(3)

All signal wiring must be run in separate steel
conduit.

A wire tray is not suitable.

The minimum spacing between conduits
containing different wire groups is 76.2 mm
(3 in.).

5

Digital circuit
(high speed)

Pulse train input

tachometer PLC

communication

Belden 8760

(1)

Belden 9460

(3)

Belden 9463

(4)

(1) 18 AWG, twisted pair, shielded

(2) 18 AWG, 3 conductor, shielded

(3) 18 AWG, twisted pair, shielded

(4) 24 AWG, twisted pair, shielded