Rockwell Automation Publication 6000-IN006A-EN-P - April 2014
25
Shipping and Handling Procedures
Chapter 1
3.
Attach the U-ring attachments to the lifting provisions on the isolation
transformer.
Figure 14 - Overhead Lifting (Isolation Transformer Cabinet)
U-rings
Steel Cable
Lifting
Provision
Support Brackets
Power cable
connection openings
to adjacent bypass
cabinet (if supplied).
Not applicable without
a bypass cabinet.
B
1/2B
ATTENTION: The cabinet is attached to the base of the isolation transformer.
The cabinet is designed to be lifted only by the isolation transformer lifting
provisions. Do not attach cables to the Isolation Transformer cabinet.
ATTENTION: Keep the weight of the isolation transformer centered when
lifting. It is recommended to use the four lifting provisions at all corners of the
isolation transformer. Alternatively, the two lifting provisions diagonally
opposed could be used.