Lift the Bypass Cabinet

If the optional Bypass Cabinet is supplied, lift the Bypass Cabinet using four M12
eye bolts. The back plate does not have to be removed to install the M12 nuts as
they are welded to the inside of the top plate. See

Torque Requirements on

page 71

for appropriate torque requirements.

1.

Install four M12 eye bolts and washers in each corner of the top plate on
the cabinet.

Figure 15 - Install Bypass Cabinet hardware

2.

Attach a steel cable or other suitable lifting rigging to the eye bolts. The
lifting rigging must meet lifting capacity requirements.

Figure 16 - Lift Bypass Cabinet

3.

When the cabinet is in the desired position, remove the steel cable, and
hardware.

4.

Replace the eye bolts with four M12 bolts and washers provided in the
document/hardware box.

M12 Eye Bolt

Welded Nut

Washer

Maximum 45º

Steel Cable