Drive Mechanical Installation
Chapter 2
Table 8 - Power Module Specifications
Figure 24 - Drawout Power Module Lifting Handles
Type
Output Rating (Amps)
Dimensions (HxWxD), approx.
Weight, approx.
Fixed-mounted
≤150 A
420 x 180 x 615 mm (16.5 x 7.1 x 24.2 in.)
20 kg (44.1 lb)
151...200 A
420 x 260 x 615 mm (16.5 x 10.2 x 24.2 in.)
25 kg (55.1 lb)
Drawout
201...380 A
575 x 342 x 691 mm (22.6 x 13.5 x 27.2 in.)
40 kg (88.2 lb)
381...420 A
575 x 342 x 910 mm (22.6 x 13.5 x 35.8 in.)
50 kg (110.2 lb)
ATTENTION: Two people are required to handle the Power Modules. Always
handle the drawout Power Modules using the two recessed lifting handles on
both mounting rails (
).
Recessed Lifting Handles
Mounting Rail
ATTENTION: Do not use the front mounted positioning handles for lifting the
Power Modules. They are designed to position or withdraw the Power Module
when on the tray assembly.