Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

35

Drive Mechanical Installation

Chapter 2

Table 8 - Power Module Specifications

Figure 24 - Drawout Power Module Lifting Handles

Type

Output Rating (Amps)

Dimensions (HxWxD), approx.

Weight, approx.

Fixed-mounted

≤150 A

420 x 180 x 615 mm (16.5 x 7.1 x 24.2 in.)

20 kg (44.1 lb)

151...200 A

420 x 260 x 615 mm (16.5 x 10.2 x 24.2 in.)

25 kg (55.1 lb)

Drawout

201...380 A

575 x 342 x 691 mm (22.6 x 13.5 x 27.2 in.)

40 kg (88.2 lb)

381...420 A

575 x 342 x 910 mm (22.6 x 13.5 x 35.8 in.)

50 kg (110.2 lb)

ATTENTION: Two people are required to handle the Power Modules. Always
handle the drawout Power Modules using the two recessed lifting handles on
both mounting rails (

Figure 24

).

Recessed Lifting Handles

Mounting Rail

ATTENTION: Do not use the front mounted positioning handles for lifting the
Power Modules. They are designed to position or withdraw the Power Module
when on the tray assembly.

Advertising