56

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

Chapter 4

Drive Electrical Interconnection

Power Cable Interconnection
Overview

Figure 35

provides a three-line drawing overview of the power cable

interconnections between the power modules (PC XX) in the Power Module/
LV Control cabinet and the secondary windings of the isolation transformer in
the Isolation Transformer cabinet. The number of power modules is dependent
solely on output (motor) voltage:

9 power modules for 3/3.3 kV

18 power modules for 6/6.6 kV

27 power modules for 10 kV

It also shows the connection point from the U, V, and W motor output phases
from the power module array to the voltage sensing board cables and the motor
cables.

The isolation transformer secondary windings as shown do reflect the actual
orientation on the isolation transformer.

The Power Module/LV Cabinet orientation is optimized for drawing clarity. To
better understand the physical orientation, the components and connections
shown in the Power Module/LV Control Cabinet would be rotated 90º counter
clockwise. The U phase is the top horizontal row, the V phase is the middle
horizontal row, and the W phase is the bottom horizontal row.

Refer to the Electrical Drawing for actual wire number designations.

Figure 35 - Power Cabling Overview (3.3 kV Fixed-mounted Power Module Configuration)

L11
L12
L13

A1

B1

C1

A2

B2

C2

A3

B3

C3

A4

B4

C4

A5

B5

C5

A6

B6

C6

A7

B7

C7

A8

B8

C8

A9

B9

C9

U

V

W

PC A1

PC A2

PC A3

PC B1

PC B2

PC B3

PC C1

PC C2

PC C3

U

V

W

Input power

3-phase AC

any voltage

Isolation Transformer

Motor

Voltage Sensing

Board

Isolation Transformer Cabinet

Power Module/LV Control Cabinet