Connect lv control and fan wiring bundles, Introduction – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 62

Advertising
background image

62

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

Chapter 4

Drive Electrical Interconnection

Connect LV Control and
Fan Wiring Bundles

Introduction

There are control wiring bundles that must be reconnected after the drive
cabinets are connected together. These control wiring bundles are connected for
the factory test and then disconnected and bundled at the shipping splits before
shipment.

Each of the four drive configurations are shown:

Fixed-mounted Power Module (without Bypass)

Fixed-mounted Power Module (with Bypass)

Drawout Power Module (without Bypass)

Drawout Power Module (with Bypass)

Each configuration shows the “as shipped” state. This shows where the wire
bundles are coiled up, where they originate, where they terminate, and whether
they are ran in the front or rear wireway. The “connected” state is also shown for
each configuration. For exact wire numbers and terminal block designations,
refer to the Electrical Drawings.

X1 to X5 refer to terminal block strips in the various cabinets.

Fixed-mounted Power Module Configuration (without Bypass)

Figure 41 - Interconnection Configuration (As shipped)

Figure 42 - Interconnection Configuration (Connected)

X2 (to X3)

Fan (to X4)

X1 (to X4)

Isolation Transformer Cabinet

Power Module/LV Control Cabinet

Top View (Front)

X2 (to X3)

Fan (to X4)

X1 (to X4)

Isolation Transformer Cabinet

Power Module/LV Control Cabinet

Top View (Front)