Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

37

Drive Mechanical Installation

Chapter 2

5.

Insert the locking key into the cam mechanism actuator and rotate
clockwise while gently pushing on the face of the Power Module.

The cam mechanism will catch the pin on the tray assembly.

6.

Continue rotating the locking key until the Power Module is fully seated.

This ensures the finger assemblies at the back of the Power Module are
fully connected to the stab assemblies at the back of the Power Module
compartment.

Locking Key

Pin

Cam Mechanism

Cabinet

Stab

Assemblies

Finger

Assemblies

SIDE VIEW

Connection to

Motor Phase Bus

Three Phase

Input Power

from Isolation

Transformer

Pin

Cam Mechanism

TOP VIEW

Locking Key

Cam Mechanism Actuator

ATTENTION: The Power Module finger assemblies must be fully seated on the
cabinet stab assemblies.

Advertising