G - line and load cable sizes, Appendix g, Line and load cable sizes – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 91: Appendix

Advertising
background image

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

91

Appendix

G

Line and Load Cable Sizes

This data is informative only; do not base final design criteria solely on this data.

Follow national and local installation codes, industry best practices, and cable
manufacturer recommendations. As cabling methods can very widely, maximum
cables sizes do not account for the size of the conduit hub.

Description
(Motor V/Freq.)

Drive Enclosure
Opening mm (in.)

Max. Size & No. Incoming
Cables: IEC

(1)

(2)

(3)

Maximum Line
Cable Sizes

3000 V, 50/60 Hz

110 (4.33)

300 mm² 5 kV or 240 mm² 8 kV/phase

3300 V, 50/60 Hz

110 (4.33)

300 mm² 5 kV or 240 mm² 8 kV/phase

6000 V, 50/60 Hz

110 (4.33)

240 mm² 8 kV or 185mm² 15 kV/phase

6600 V, 50/60 Hz

110 (4.33)

240 mm² 8 kV or 185mm² 15 kV/phase

10,000 V, 50/60 Hz

110 (4.33)

185 mm² 15 kV/phase

Maximum Load
Cable Sizes

3000 V, 50/60 Hz

110 (4.33)

300 mm² 5 kV or 240 mm² 8 kV/phase

3300 V, 50/60 Hz

110 (4.33)

300 mm² 5 kV or 240 mm² 8 kV/phase

6000 V, 50/60 Hz

110 (4.33)

240 mm² 8 kV or 185mm² 15 kV/phase

6600 V, 50/60 Hz

110 (4.33)

240 mm² 8 kV or 185mm² 15 kV/phase

10,000 V, 50/60 Hz

110 (4.33)

185 mm² 15 kV/phase

(1) Cable sizes are based on overall dimensions of compact-stranded three-conductor shielded cable (common for industrial cable tray

installations). Maximum sizing stated accounts for minimum rated cable insulation requirements and the next higher-rated cable
(i.e., 8 kV is not commercially available in many areas of the world, therefore Rockwell Automation provides an 8 kV (minimum
rating) as well as a 15 kV rating, when applicable. Enclosure openings will accommodate the thicker insulation on the higher-rated
cable. IEC ratings show the equivalent to the NEMA sizes. The exact cable mm

2

size shown is not commercially available in many

cases; use the next smaller standard size.

(2) Minimum cable bend radius recommendations vary by national codes, cable type, and cable size. Consult local codes for guidelines

and requirements. General relationship of cable diameter to bend radius is typically between 7x...12x (e.g., if the cable diameter is 1
in. [2.54 cm] the minimum bend radius could range between 7...12 in. [18.8...30.48 cm]).

(3) As cabling methods can vary widely, maximum cable sizes shown do not account for the size of the conduit hub. Verify size of

conduit hub(s) against the “Drive enclosure openings” shown.