Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 90

Advertising
background image

90

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

Appendix F

Power Cabling and Control Signal Wiring Details

All of the AI/AO, DI/DO connection points are expandable based on user requirements.

VFD alarm indication (905, 906)

1

VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)

VFD fault indication (907, 908)

1

VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)

VFD operation indication (909, 910)

1

VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)

VFD stop indication (911, 912)

1

VFD-provided normally closed passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)

VFD ready indication (913, 914)

1

VFD-provided normally closed passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)

Remote DCS control indication (915, 916)

1

VFD-provided normally closed passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)

13

VFD allow closing indication (135, 121)

1

VFD-provided normally closed active dry contact
(voltage class ≤220V AC, 5A) (spare)

Input circuit breaker closing indication (136,
121)

1

VFD-provided normally closed active dry contact
(voltage class ≤220V AC, 5A) (spare)

Input circuit breaker opening indication
(137, 121)

1

VFD-provided normally closed active dry contact
(voltage class ≤220V AC, 5A) (spare)

VFD alarm indication (138, 121)

1

VFD-provided normally open active dry contact
(voltage class ≤220V AC, 5A) (spare)

VFD fault indication (139, 121)

1

VFD-provided normally open active dry contact
(voltage class ≤220V AC, 5A) (spare)

VFD operation indication (140, 121)

1

VFD-provided normally open active dry contact
(voltage class ≤220V AC, 5A) (spare)

VFD stop indication (141, 121)

1

VFD-provided normally open active dry contact
(voltage class ≤220V AC, 5A) (spare)

VFD ready indication (142, 121)

1

VFD-provided normally open active dry contact
(voltage class ≤220V AC, 5A) (spare)

Spare (143, 121)

1

VFD-provided normally open active dry contact
(voltage class ≤220V AC, 5A) (spare)

Spare (120, 121)

1

VFD-provided 220V AC (load ≤10 W, spare)

Table 32 - I/O Connections related to Remote Distributed Control System (Continued)

Serial Number

Name of I/O Connection

AI

AO

DI

DO

Note