Drive Electrical Installation

Chapter 3

Electrical Installation
Summary

Connect the System Ground
Cable

The drive ground bus runs along the bottom of the drive at the front. The ground
bus is accessible at the bottom of the front of each drive cabinet when the cabinet
door is opened. Connect the system ground cable to the drive ground bus
(

Figure 27

).

Figure 27 - Ground Cable Connection in the Isolation Transformer Cabinet

Megger Test of Power Cables

Before connecting the incoming line and outgoing motor power cables, follow
standard industry practice to verify the integrity of the power cable insulation
from the input breaker to the drive and from the drive to the motor.

Connect Incoming Line and
Outgoing Motor Power
Cables

The installer must ensure that all power connections are in accordance with
national and local electrical codes.

Each drive is equipped with provisions for bottom power cable entry as standard.
Provisions for top power cable entry can also be provided. This must be specified
at the time of order.

Connect External Cabling and Wiring

Page

Connect the System Ground Cable

47

Megger Test of Power Cables

47

Connect Incoming Line and Outgoing Motor Power Cables

47

Connect Control Power Wiring

50

Connect External Control Signal Wiring

52

Connect Electrical Safety Interlock Circuit to Input Circuit Breaker

53

M8*25 Bolt

M8 Nut

Lock Washer

Flat Washer

Customer/Contractor supplied

System Ground Cable

Ground Bus

IMPORTANT

If an optional Bypass cabinet is supplied, the system ground cable connection
is in the Bypass cabinet. Refer to publication 6000-UM002_-EN-P.