Standard input/output connection points, Table 31, Table 32 on – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

89

Power Cabling and Control Signal Wiring Details

Appendix F

Standard Input/Output
Connection Points

Table 31 - I/O Connections related to High Voltage Cabinet

Serial Number

Name of I/O Connection

AI

AO

DI

DO

Note

1

Input circuit breaker closing node is allowed
(917, 918)

1

Serially connected into the input circuit breaker's closing circuit (the VFD
provides passive normally open points, valid when closed)

2

Trip connection points within the VFD
(919, 920)

1

Can be connected into input circuit breaker's closing circuit in parallel (the VFD
provides passive normally open points, valid when closed)

3

Input circuit breaker already closed
connection point (117, 119)

1

Circuit breaker's auxiliary normally open connection points (valid when closed)

Table 32 - I/O Connections related to Remote Distributed Control System

Serial Number

Name of I/O Connection

AI

AO

DI

DO

Note

1

VFD speed regulation command (931, 402)

1

User-provided 4...20mA

Spare (932, 402)

1

User-provided 4...20 mA (spare)

Spare (934, 402)

1

User-provided 4...20 mA (spare)

Spare

1

User-provided 4...20 mA (spare)

2

VFD speed feedback signal (927, 928)

1

VFD-provided 4...20mA

3

VFD current feedback signal (925, 926)

1

VFD-provided 4...20mA

4

Alternate start command signal (431, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

Remote DCS start command signal (449,
401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

5

Alternate stop command signal (432, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

Remote DCS stop command signal (450, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

6

Spare (433, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

7

Spare (434, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

8

Spare (435, 401)

1

User-provided normally open passive dry contact (switch quantity)

Spare (436, 401)

1

User-provided normally open passive dry contact (switch quantity)

Spare (437, 401)

1

User-provided normally open passive dry contact (switch quantity)

Spare (438, 401)

1

User-provided normally open passive dry contact (switch quantity)

9

Remote DCS alternate (448, 401)

1

User-provided normally open passive dry contact (switch quantity)

10

Remote DCS fault reset command (412, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

Alternate reset command (412, 401)

1

User-provided normally open passive dry contact
(pulsed quantity, valid with 3S)

11

Emergency stop button command
(1101, 1102)

1

User-provided normally closed passive dry contact
(voltage class higher than 220V AC, 5 A, switch quantity)

12

VFD allow closing indication (901, 902)

1

VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5 A) (used for Remote DCS)

Circuit breaker closing indication (903, 904)

1

VFD-provided normally open passive dry contact
(voltage class ≤220V AC, 5A) (used for Remote DCS)