Chapter 1

Shipping and Handling Procedures

Mounting Clearance Distance

Install the drive with appropriate clearance distances on all sides to ensure proper
operation and allow maintenance of the drive.

Mounting Requirements

The base must be smooth, flat and level. If power cabling is entering from below,
and a cable trench system is used, refer to

Figure 3

. The base structure of the drive

cabinet may be constructed with #10 channel steel, approximately
100 x 48 x 5.3 mm (3.9 x 1.9 x 0.2 in.). Dimension pairs reflect the 1300 mm or
1500 mm deep cabinet configurations and the corresponding Drive Cable
Trench depth. See

Appendix on page 75

.

Figure 3 - A typical cross-sectional view of the trench system

Embed the channel steel base profile in the base with its top surface flush with
ground level, or protruding slightly above ground level.

Table 3 - Minimum Mounting Clearance Distances

Location

Minimum Distance Required, approx.

In Front

1500 mm (60 in.)

Behind

1000 mm (39 in.)

Above

(1)

(1) Distance above is measured from the top plate of the drive cabinet (excludes height of fan housing).

400 mm (16 in.) without ducting requirements
1000 mm (39 in.) with ducting requirements

ATTENTION: An incorrectly applied or installed drive can result in component
damage or reduction in product life. Ambient conditions not within the
specified ranges may result in malfunction of the drive.

150 mm

(6 in.)

950 mm (37 in.) or

1150 mm (45 in.)

1300 mm (51 in.) or

1500 mm (59 in.)

Cabinet body is

bolted to the

channel steel base

Main Cable Trench

Cable Passage

Drive Cable Trench

Back

Front

Channel Steel Base