Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

29

Drive Mechanical Installation

Chapter 2

Figure 18 - Aligning Cabinets with Drawout Power Modules (6/6.6 kV shown)

Isolation Transformer Cabinet

Power Module/LV Control Cabinet

Bypass Cabinet

(Optional)

Table 6 - Sidesheet Openings

Front Wireway

Rear Wireway

U Phase Motor Cable

V Phase Motor Cable

W Phase Motor Cable

Ground Bus Connection

Voltage Sensing
Board Cables

Isolation Transformer Secondary
Cables

(1)

(2)

(1) The number of Isolation Transformer secondary

cables is dependent on motor voltage class.
• 9 cables per motor phase (27 total) for 3/3.3 kV
•18 cables per motor phase (54 total) of 6/6.6 kV
• 27 cables per motor phase (81 total) for 10 kV

(2) 6/6.6 kV configurations only require 18 cable

hole locations per phase. Extra cable hole
locations allow for added installation flexibility.

❸❹❺

Front

Front

SIDE VIEW