Install main cooling fans – Rockwell Automation 6000 PowerFlex Medium Voltage Variable Frequency Drive Installation Instructions User Manual

Page 33

Advertising
background image

Rockwell Automation Publication 6000-IN006A-EN-P - April 2014

33

Drive Mechanical Installation

Chapter 2

Install Main Cooling Fans

Main cooling fans are shipped in separate crates (

Table 1

). The fans are shipped

assembled in the fan housing, but must be installed after siting the drive.

Most drive configurations will have two to five fans. Higher power configurations
will have a higher number of fans. Refer to

PowerFlex 6000 Dimensions and

Weights on page 75

for fan quantities and dimensions.

Table 7 - Fan Housing Specifications

1.

Place the fan housing on the top plate of the drive, making sure the socket
is on the same side as the aviation plug.

2.

Secure the fan housing using M6 hardware (6 places).

See

Torque Requirements on page 71

.

3.

Connect the aviation plug located on top of the cabinet with the socket on
the fan housing.

Figure 22 - Main Cooling Fan Housing

IMPORTANT

See

Mounting Clearance Distance on page 16

to verify that the fans have the

appropriate clearance distance on top of the cabinet.

Model

Dimensions (HxWxD), approx.

Weight, approx.

RH40M

330 x 440 x 500 mm (13.0 x 17.3 x 19.7 in.)

20 kg (44.1 lb)

RH45M

370 x 490 x 550 mm (14.6 x 19.3 x 21.7 in.)

25 kg (55.1 lb)

Main Cooling Fan Housing

M6 Hardware
(6 places per fan)

Aviation Plug

Socket

Rear View