Drive Mechanical Installation
Chapter 2
Affix Cabinets to Floor
Typical floor drawings show minimum clearance distance, conduit openings, and
mounting holes for anchor bolts
(1)
, as shown in
. Refer to project-
specific Dimensional Drawings for actual locations.
Figure 19 - Typical Floor Drawing (Fixed-mounted Power Module Configuration)
Secure the cabinet to the channel steel base using M16 bolt, lock washer, two flat
washers and a nut.
Figure 20 - Bolt Cabinet to Steel Base
(1) Mounting holes are represented as + in
.
Isolation Transformer Cabinet
Bypass Cabinet
(optional)
Power Module/LV Control Cabinet
Outgoing Motor Cable opening
Incoming Line Cable opening
Control Signal Wiring and
Control Power Cable openings
M16 Bolt
Flat Washer
Lock Washer