Terminal status indicators – Rockwell Automation 2706-M1 MESSAGEVIEW 421 HARDWARE MANUAL User Manual

Page 111

Advertising
background image

7–3

Troubleshooting and Maintenance

Publication 2706–816

The MessageView terminal has two LEDs which function as
terminal status indicators. These two indicators can be seen at the
back of the MessageView terminal as shown below.

Back View

COMM Indicator (Green)

FAULT Indicator (Red)

Use this table to interpret the state of the Status LEDs.

LED

Status

Description

What to do about it

On (Steady Green)

Normal operating state

No problem.

COMM.

Off (power applied, but
LED not lit)

Communication fault detected:

Controller does not have RIO enabled

Baud rates on terminal do not match those of

the controller

Rack settings between terminal and controller

do not match

RIO terminal connections incorrect

Check controller settings
Set controller baud rate to match the terminal
setting. See Page 3–5.
Set controller rack settings to match the
terminal settings. See Page 3–5.
Check the RIO hardware connections.

Blinking

Communications not established:

Controller/Scanner is in Program Mode

Communications not established
Controller/Scanner is in Program Mode

FAULT
(hardware)

On (Steady Red)

Terminal hardware fault detected:

Hardware fault

Firmware fault

Cycle power to the terminal so it will run its
Power-On Self Tests (POST). See Page B–4.
Cycle power to the terminal so it will run its
Power-On Self Tests (POST). See Page B–4.

Off (power applied, but
LED not lit)

Normal operating state

No problem.

The status of these indicator LEDs can also be determined through
Front Panel Editor (FPE) System Status options. See Page 3–35.