Installing the MessageView Terminal
Publication 2706–816
Make sure that you leave adequate room for mounting and air flow.
All Terminals
Leave 1 inch (25mm)
for Mounting and Air Flow
Leave 1 inch (25mm)
for Mounting and Air Flow
TERMINAL CUTOUT
for Mounting and Air Flow
Leave 5.0 inches (127 mm)
for Mounting and Wiring Connections
Use Full Size Template at End of Manual
Front View
Side, Top and Bottom Clearances
Leave 1 inch (25 mm)
Back Clearance
Leave 1 inch (25mm)
for Air Flow
Clearances