5–9

Installing the MessageView Terminal

Publication 2706–816

To connect DC power to the terminal:

1. Unplug the 3-position removeable terminal block from the

bottom rear of the terminal.

Note: A terminal block connector plug is provided with each
terminal. For additional plugs, order Replacement Part No.
22112-232-01.

2. Secure the DC power wires to the removeable terminal block via

the terminal block screws.

!

ATTENTION: Improper wiring of the power
terminals and Earth Ground may result in the
terminal malfunctioning. Refer to power connection
diagrams below when wiring.

Terminal Block Recommendations

Wire Size:

12-22 AWG

Strip Length:

.28 inches (7 mm)

Torque:

4.5 lbs./in (0.5 Nm)

DC Positive
DC Negative
Earth Ground

3. Secure the Earth Ground wire to the removeable terminal block

via the terminal block screws.

Important: Connect the Earth Ground wire to the nearest

solid earth ground. Earth ground signal path
should be as short as possible.