Led indicators – Rockwell Automation 2706-M1 MESSAGEVIEW 421 HARDWARE MANUAL User Manual

Page 72

Advertising
background image

4–12

Running Applications

Publication 2706–816

Messages with enabled function keys are terminated by:

pressing an enabled function key (non-jog)

pressing the Plus/Minus

key and Zero

0

key

simultaneously

pressing the up arrow

, down arrow

and Enter

keys

simultaneously (resetting the terminal)

controller sending a Clear Display command (Special Message
9901)

controller sending a Reset Terminal command (Special Message
9903).

Note: The application designer needs to inform the operator which
messages are non–jog and which are jog.

MessageView 421F Terminals (Catalog No. 2706-M1F1 and -M1F)
have a red LED located next to each function key. An LED can be
assigned (tagged) to a specific output bit of a logic controller by the
application.

LED Operation

An LED may be assigned one of two functions:

1. To provide visual feedback to the operator when an associated

function key is pressed (indicator tag not assigned).

2. To allow the logic controller to indicate a process status to an

operator without displaying a message (indicator tag is assigned).

Indicator Tag Not Assigned

When the LED indicator is not assigned to an output bit, then the
LED follows the state of the associated function key (F1 = LED1,
F16 =LED16). For example, LED4 will light when function key F4
is pressed.

Indicator Tag Assigned

When the LED indicator is assigned (tagged) to an output bit, then
the LED indicators operate independently of the function keys. For
example, pressing and releasing function key F1 will have no effect
on the operation of LED1.

LED Indicators