Remote I/O and RS-232 Connections

Publication 2706–816

To connect the MessageView terminal to a Remote I/O scanner, use
cable Catalog No. 1770-CD (equivalent to Belden 9463).

Refer to the Programmable Controller Wiring and Grounding
Guidelines (Publication 1770-4.1). The user manual for the I/O
scanner module also provides cabling information.

The maximum cable length (link distance) is determined by the baud
rate:

RIO port

Communicates at:

Nodes Supported

Maximum

Cable Length

Line Termination

Resistor

57.6K baud

16

10,000 ft. (2800 m)

150 ohm

115.2K baud

16

5,000 ft. (1400 m)

150 ohm

230.4K baud

32

2,500 ft. (700 m)

82 ohm

A terminal block connector plug is provided with each terminal. For
additional connector plugs, order Replacement Part No.
22112-046-03.

Remote I/O Port Connection

Cable (Catalog No. 1770-CD)

To PLC or Scanner Remote I/O Port

Line Two

Shield

Line One

Connector

(One provided with terminal)

Termination Resistor

Remote I/O Connections