Running Applications

Publication 2706–816

MessageView terminals without daughterboards (Catalog Numbers
2706-M1D, -M1N, or -M1F) are controlled by ASCII Triggering
devices.

ASCII Triggering devices include the following Allen-Bradley
products:

SLC 5/03

, 5/04

Port 0

SLC BASIC Module

PLC-5 Port 0

other logic controllers with serial ports

Allen-Bradley Industrial Computers

any ASCII Transmitting device, including a VT100 Dumb
Terminal.

Follow this procedure to set up the MessageView terminal with an
ASCII Triggering device as the controller:

1. Download a MessageBuilder application to the MessageView

terminal.

2. Connect the terminal to the ASCII Triggering device via a 485

network. See the diagrams and pinouts in Chapter 6.

3. Access the Front Panel Editor by simultaneously pressing the up

and down

arrow keys on the terminal keypad.

4. Verify that the terminal’s RS-232 port is set to ASCII Trigger. See

Page 3–3.

5. Check that the Serial Communication parameters match those of

the ASCII Triggering device. See Page 3–8.

6. Exit the Front Panel Editor. The terminal starts to run its

application.

Messages to the MessageView terminal

Trigger a message with [Ctrl-T]

Used by the ASCII Triggering device to trigger a specific message.

Format: [Ctrl-T]Message#\ MV Address[CR]

Message# range: 1 to 9999; limited to the subset used in the
application

MV Address range: 1 to 127 for a single node; 127 to address all
devices

Example: [Ctrl-T]24\ 6[CR]

The terminal at node #6 displays message #24 in the downloaded
application