Interface

Chapter 7
Host Commands Using the RS-232 or RS-422

7–10

Example:

Command:

IM2#1

Response:

=00LF

Comments:

2 = message length.
#1 = source identification message.
00 = “command complete” response code.
LF = end of message control code for Line Feed.

Command:

MCn

Function:

Reads the output counter.

Response:

mmmmmm<end>=rr<end>

Comments:

MC = Read output counter command.

n = output counter. This value must be from 1 through 8.

mmmmmm = output counter count. Maximum value of
999999.

<end> = end of message code.

rr = response code, refer to Table 7.B.

<end> = end of message code.

Example:

Command:

MC3

Response:

000121LF=00LF

Comments:

000121 = Output #3 has been activated 121 times since the
last restart or reset.
LF = end of message code for Line Feed
00 = “command complete” response code
LF = end of message code for Line Feed

Command:

MFabcdefgdddssshx

Function:

Specifies the format of messages.

9. Read Output Counter

10. Set Message Format