Chapter 3
How the Decoder Operates

3–3

AC Output Module Application

Figure 3.3 illustrates a typical AC output module application. When using
high impedance loads, you may have to add an additional resistor (Rx) in
parallel with the load. Select a value for Rx that maintains a minimum
current of 50 mA RMS through the output module in the on state.

Figure 3.3
AC Output Module Application

AC SOURCE

Rx

DECODER

LOAD

CONNECTOR BLOCK

AC

OUTPUT MODULE

FUSE

Input Module Auto Load Application

Figure 3.4 illustrates the auto load input module application.

Figure 3.4

Typical Input Module Auto Load Application

MODULE LOCATION #8 ONLY

AC or DC SOURCE

-

+

Auto Load
Pushbutton

DECODER

CONNECTOR BLOCK

INPUT MODULE
AC or DC

FUSE

As stated earlier the decoder can transmit decoded bar code information to a
host computer or programmable controller. The three communications

Communications