Appendix A
Setting Up the Programming Terminal

A–3

The Catalog No. 1784-T45 Programming Terminal may be used to program
the 2755-DM9, -DM9E decoder. Set the T45 Terminal Emulation to the
following:

F1DGC D200 Terminal

F2Modem = External

F3Flow Control = On

F4Duplex = Full

F6Print = Off

Set the COM 1 parameters to:

F1Baud = 9600

F2Parity = None

F3Data Bits = 8

F4Stop Bits = 1

F5Type = Standard PC Compatible Com

Note: If an internal modem is being used, it must be disabled using the
MODE command.

Fabricate the cable shown in Figure A.4.

Figure A.4
Connections for Cable Used with 1784-T45 Terminal

DTR

CD

DSR

CTS

AUX Port on Decoder-DCE

Note

:

Connect shield to shell of

cable connectors at both ends.

2

3

7

2

3

Transmit Data

Receive Data

Cable:
Belden 9939 or
equivalent

7

8

20

RTS

1784-T45-DTE Device

With DG D200 emulation.

6

5

4

Signal Ground

When the

Select CRT Type

menu appears, select Data General D200

emulation.