Set scanner control – Rockwell Automation 2755-DM9, -DM9E High Speed Decoder User Manual

Page 111

Advertising
background image

Interface

Chapter 7
Host Commands Using RS-232 or RS-422

7–19

Command:

SCldcsprrrrttttm

Function:

Specifies operating parameters of the scan head.

Response:

=rr<end>

Comments:

SC = Scanner control command.

l = laser-on mode:
0 = Continuous
1 = Triggered

d = trigger mode:
0 = Package Detect
1 = Host Command
2 = Internal Timer
3 = Continuous

c = capture count. Count must be a value from 1 through 8.

s = number of bar code fields per scan. This entry must be a
value from 0 through 4. A value of 0 = ANY 1, 2, 3, or 4).

p = number of bar code fields per package. Must be a value
1 through 8.

rrrr

= no-read timer value in milliseconds. Must be value

from 0010 to 9999. A value of 0000 will disable the timer.

tttt = inter-scan timer value in milliseconds. Must be value
from 0010 to 9999. A value of 0000 will disable the timer.

m = match complete count. Must be value from 1 through 8.

Note: Refer to Chapter 4 for a description of scanner control
parameters.

<end> = end of message code.

rr = response code, refer to Table 7.B.

Example:

Command:

SC01211005500601

Response:

=00CR

Comments:

0 = Continuous scanning
1 = Host command.
2 = Capture count of 2 set.
1 = one bar code field per scan.
1 = one bar code field per package.
0055 = No-read 55 millisecond timer.
0060 = Inter-scan timer value of 60 milliseconds.1 = match
complete count of one.
00 = “command complete” response code.
CR = end of message code for carriage return.

23. Set Scanner Control