1-6

Installation/Wiring

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

Table 1.B Active Converter Control PCB Assembly P1 Terminal Descriptions

Table 1.C Voltage Feedback Resistor PCB Assembly P2 Terminal Descriptions

Specific pins on P1 and P2 terminals require control wiring connections to
the Input Filter Bay. For wiring information, please refer to the PowerFlex
700L Liquid-Cooled Adjustable Frequency AC Drive User Manual
(Publication No. 20L-UM001…).

Using the Active Converter as a Coupled Unit vs. Standalone Unit

Frame 3B converter power structures may be ordered as a unit Coupled to
an inverter (DPI SLAVE), or as a Stand Alone unit (DPI MASTER). Frame
2 and Frame 3A power structures are always wired for the converter to be a
Coupled unit.

Coupled

Figure 1.4

shows the Active Converter wired to operate as a Coupled unit

(DPI SLAVE). In this configuration, the Converter is connected to a
PowerFlex 700L Inverter through DPI Port 6. When configured for "Run On
Start," the Converter is able to start and stop automatically as the Inverter is
started and stopped.

Pin

Description

1

Comm Out +

2

Comm Out -

3

SOC Out +

4

SOC Out -

5

Comm In +

6

Comm In -

7

SOC In +

8

SOC In -

9

Aux Out N.O.

10

Aux Out Common

11

Analog In Signal

12

Analog In Common

13

Gate Enable

14

24 Vdc

15

Aux Input

Pin

Description

7

L3

4

L2

1

L1