Programming and Parameters

3-7

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

CO

MMA

N

D

Star

t /

Stop

053

[Turn Off Delay]

This parameter is used when parameter 50 - [Start Config] is set to “0” (Run On
Start) to select how long to keep the Converter enabled after the Inverter is
stopped.

Default:

Min/Max:
Units:

5.0 Sec

1.0/60.0 Sec
0.1 Sec

Setpoints

060

[DcLink Reference]

Sets the reference for the DC Link voltage when parameter 160 - [Voltage Loop
Sel] is set to “1” (Manual Ref).

Default:

Min/Max:
Units:

Rated*1.46 Vdc

300.0/1100.0 Vdc
0.1 Vdc

061

[kVAR Reference]

Sets the reference for the kVAR to produce. Positive values are a leading power
factor and negative values are a lagging power factor.

Default:

Min/Max:
Units:

0.0 KVAR

–3000.0/+3000.0 KVAR
0.1 KVAR

062

[Extern Cml Ref]

Sets the current reference as calculated by an external voltage loop. Values are
scaled so 4096 corresponds to Converter rated current.

Default:

Min/Max:
Units:

0

–8192/+8192
None

063

[Modulation Index]

Sets the modulation duty cycle when parameter 51 - [Option Select] Bit 4 Sim
ModIndex is enabled and the Converter is started.

Default:

Min/Max:
Units:

0.0%

0.0/100.0%
0.1%

064

[Modulation Freq]

Sets the simulated line frequency when parameter 51 - [Option Select] Bit 5 Sim
ModFreq is enabled and the Converter is started.

Default:

Min/Max:
Units:

0.0 Hz

0.0/60.0 Hz
0.1 Hz

Da

ta

E

xch

ang

e

070

[Converter Control]

A set of bits sent from the Inverter to control the Converter.

Bit 0 (Enable Cnvtr) – This bit is set by the Inverter when the drive is started. When parameter 50 - [Start Config] is set to “0” (Run
on Start), setting this bit closes the precharge bypass and enables the Converter voltage and current loops.

Bit 1 (700VC Invtr) – This bit is set when the Active Converter is communicating with an Inverter that has 700 Vector Control. It is
cleared when communicating with an Inverter that has 700S Phase II Control.

Fil

e

Gr

oup No.

Parameter Name & Description

Values

Bit
Definition

700VC In

vtr

En

ab

le Cn

vtr

Default

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled
x = Reserved