Using a 20-COMM-x Adapter

When a 20-COMM-x network communication adapter is connected to the
Converter, the Product Logic Command bits may be used to start and stop
the Converter and to reset a fault. All other bits are reserved. The Product
Logic Status bits may be used to determine the state of the Converter.

Converter Logic Command Word

Converter Logic Status Word

The reference value from the 20-COMM-x adapter that is often used to
select the speed is not used in the Converter. The Converter is always

Logic Bits

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0 Command

Description

x

Stop

0 = Not Stop
1 = Stop

x

Start

0 = Not Start
1 = Start

x

Reserved

x

Fault Reset

0 = Not Fault Reset
1 = Fault Reset

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

Logic Bits
15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Status

Description

x

Ready

0 = Not Ready
1 = Ready

x

Running

0 = Not Running
1 = Running

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Alarm

0 = No Alarm
1 = Alarm

x

Fault

0 = No Fault
1 = Fault

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved

x

Reserved