Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 24

Advertising
background image

2-6

Start Up

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

In addition to Type 3 communication, the 700S may optionally use DPI data
links to control the sequencing of the Converter from a Logix processor as
shown below. This requires the Converter to be configured for Manual
Control in Converter parameter 50 - [Start Config]. The reference for the
voltage loop may also be controlled by a Logix processor when Converter
parameter 160 - [Voltage Loop Sel] is set to Manual Ref.

The DPI data links between the Inverter and Converter are enabled by
setting Converter parameters 300 - [Data In A1] through 317 - [Data Out
D2] to the parameter number of the data to send or receive. When a DPI
data link is used by the Converter, that channel cannot be used by a different
communication card. The following example illustrates using DPI data links
between the Inverter and Converter.

Suppose Inverter parameter 666 is linked to Converter parameter 52 -
[Manual Control], Inverter parameter 667 is linked to Converter parameter
60 - [DcLink Reference], and Converter parameter 71 - [Converter Status] is
linked to Inverter parameter 657. This requires Converter data links to be
configured as follows:

Active Converter parameter 306 [Data In D1] = 52

Active Converter parameter 307 [Data In D2] = 60

Active Converter parameter 316 [Data Out D1] = 71

This example shows Data Link D being used to communicate with the
Converter. The Converter supports DPI Data Links A, B, C, and D so any
group could be used as needed.

All the options for starting and stopping the Converter are explained in
greater detail in

Converter Sequencing on page 2-12

.

PF700 S
Parameters

S 657 - [DPI Data In D1]

S 666 - [DPI Data Out D1]

Logix

Converter DPI Data Link

Producer / Consumer

Inverter DPI Data Link

Producer / Consumer

AC 60 - [DcLink Reference]

AC 71 - [Converter Status]

Converter
Communications

Inverter
Communications

Converter Sequencing

Precharge

Contactor

Converter

Enable

AC 52 - [Manual Control]

S 667 - [DPI Data Out D2]

PF700 AC
Parameters

Converter
Functions