3-12

Programming and Parameters

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

D

Y

NA

MI

C C

O

NTR

O

L

V

o

lta

g

e Loop

162

[Capacitance]

Sets the DC Link capacitance. When set to non-zero, this value is used to
calculate the tuning coefficients for the voltage loop VML Ki and Kp. In the case
of a Frame 2 or Frame 3A drive, this is the capacitance inside the drive. In the
case of a Frame 3B drive, it is the capacitance in the Converter and one Inverter.
The capacitance of any additional Inverters connected to a common bus must
be entered in parameter 170 - [Bus Capacitance].

Default:

Min/Max:
Units:

Rated µF

0/65535 µF
1 µF

163

[VML Bandwidth]

Sets the Voltage Major Loop bandwidth. When set to non-zero, this value is
used to calculate the tuning coefficients for the voltage loop VML Ki and Kp.

Default:

Min/Max:
Units:

400 Rad/sec

0/800 Rad/sec
1 Rad/sec

164

[VML Damping]

Sets the Voltage Major Loop damping. When set to non-zero, this value is used
to calculate the tuning coefficients for the voltage loop VML Ki and Kp.

Default:

Min/Max:
Units:

1.6

0.5/5.0
None

165

[VML Ki]

Tunes the integral gain of the voltage loop.

Default:

Min/Max:
Units:

Drive Size Dependent

0/32767
None

166

[VML Kp]

Tunes the proportional gain of the voltage loop.

Default:

Min/Max:
Units:

Drive Size Dependent

0/32767
None

167

[VML Kf]

Tunes the feed forward gain of the voltage loop.

Default:

Min/Max:
Units:

0

0/32767
None

168

[VML Reset Level]

Sets the voltage error when to reset the integrator.

Default:

Min/Max:
Units:

60.0 Vdc

10.0/300.0 Vdc
0.1 Vdc

169

[Parallel Config]

Reserved for future.

Default:

Options:

0

0
1
2
3
4

“Stand Alone”

“Stand Alone”
“Master of 1”
“Master of 2”
“Master of 3”
“Follower”

170

[Bus Capacitance]

Sets the additional capacitance connected to the DC link in a common bus
application. This value, in addition to the value of parameter 162 - [Capacitance],
sets the tuning coefficient for the voltage loop VML Ki and Kp.

Default:

Min/Max:
Units:

0 µF

0/2000000000 µF
1 µF

Fil