Programming and Parameters

3-13

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

Utility File

Fil

e

Gr

oup No.

Parameter Name & Description

Values

UTILITY

Dr

iv

e Me

mor

y

196

[Param Access Lvl]

Selects which parameters are accessible by the HIM.
“Basic” = A minimal subset of parameters are accessible on the HIM.
“Advanced” = All parameters are accessible on the HIM.

Default:

Options:

0

0
1

“Basic”

“Basic”
“Advanced”

197

[Reset to Defaults]

Resets all values in the Converter to the factory defaults.
“Ready” = A new value may be entered.
“Factory” = Parameters are reset.

Default:

Options:

0

0
1

“Ready”

“Ready”
“Factory”

200

[Reset Meters]

Resets the elapsed kWh and run time parameters to zero.

“Ready” = A new value may be entered.
“kWh” = The kWh accumulators are reset to zero.
“Elapsed Time” = The Time accumulators are reset to zero.

Default:

Options:

0

0
1
2

“Ready”

“Ready”
“kWh”
“Elapsed Time”

201

[Language]

Selects the language in which all text is displayed.

Default:

Options:

0

0
1
2
3
4
5
7
10

“Not Selected”

“Not Selected”
“English”
“French”
“Spanish”
“Italian”
“German”
“Portuguese”
“Dutch”

203

[Drive Checksum]

Displays the checksum of all the parameters in the Converter. This provides a quick way
to know if any parameter has been changed.

Default:

Min/Max:
Units:

Read Only

0/65535
None

204

[Control SW Ver]

Displays the software version of the Converter.

Default:

Min/Max:
Units:

Read Only

0/65.535
None

205

[Password]

Value entered here to enable protected feature.

Default:

Min/Max:
Units:

0

0/65535
None

Diagnostic

211

[Alarm Status]

A set of bits displaying the alarms active in the Converter.

Bit 0 (Ac Low Volt) is set when the average AC line voltage is less than the limit in parameter 112 - [Low Vac Lmt].

Bit 1 (Ac High Volt) is set when the average AC line voltage exceeds the limit in parameter 114 - [High Vac Lmt].

Bit 2 (Ac Low Freq) is set when the AC line frequency is less than the limit in parameter 131 - [AC Low Freq Lmt].

Bit 3 (Ac High Freq) is set when the AC line frequency exceeds the limit in parameter 133 - [AC High Freq Lmt].

Bit 4 (Ac High dFdt) is set when the AC line frequency is changing faster than the limit in parameter 135 - [AC Maximum dF/dt].

Bit 5 (I Imbalance) is set when the phase current imbalance exceeds the limit in parameter 103 - [I Imbalance Lmt].

Bit 6 (V Imbalance) is set when the phase voltage imbalance is greater than the limit in parameter 116 - [V Imbalance Lmt].

Bit 7 (IT Overload) is set when the overload counter is greater than 90%.

Bit 8 (Ambient Temp) is set when the ambient temperature exceeds the limit in parameter 120 - [Ambnt Temp Alrm].

Bit 9 (Base Temp) is set when the IGBT base temperature exceeds the limit in parameter 122 - [Base Temp Alrm].

Bit 10 (Junction Temp) is set when the IGBT junction temperature exceeds the limit in parameter 124 - [Junct Temp Alrm].

Bit 11 (Coldplate Temp) is set when the coldplate temperature is less than the limit in parameter 126 - [CldPlt Temp Alrm].

Bit 12 (PWM SyncLoss) is set when PWM carrier synchronization is lost.

Bit 15 (Start Inhibit) is set when one or more start inhibits are present.

Bit
Definition

Sta

rt

Inhibit

PWM Sy

ncL

oss

Coldplat

e T

emp

Ju

nc

tion

T

em

p

Base

T

emp

Ambient

T

emp

IT

Ov

er

lo

ad

V I

m

ba

la

nce

I I

m

balanc

e

Ac High dFdt

Ac High F

re

q

Ac Lo

w

Fr

eq

Ac High V

olt

Ac Lo

w

V

olt

Default

0

x

x

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled
x = Reserved

Read Only