Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual

Page 51

Advertising
background image

Programming and Parameters

3-15

PowerFlex 700L Active Converter Power Module User Manual

Publication PFLEX-UM002D-EN-P

UTI

L

ITY

Dia

g

nostic

230

[Fault Base Temp]

Displays the IGBT base temperature at the time of the fault.

Default:

Min/Max:
Units:

Read Only

-40.0/+150.0
0.1°C

234

[Testpoint 1 Sel]

Allows for access to other test points in the system.

Default:

Min/Max:
Units:

499

0/65535
1

235

[Testpoint 1 Data]

Displays the data selected in parameter 234 - [Testpoint 1 Sel].

Default:

Min/Max:
Units:

Read Only

-2147483647/+2147483647
1

236

[Testpoint 2 Sel]

Allows for access to other test points in the system.

Default:

Min/Max:
Units:

499

0/65535
1

237

[Testpoint 2 Data]

Displays the data selected in parameter 236 - [Testpoint 2 Sel].

Default:

Min/Max:
Units:

Read Only

-2147483647/+2147483647
1

Fa

u

lt

Q

u

eu

e

238

[Fault Config]

A set of bits that select which conditions may generate faults.

Bit 0 (Ac Low Volt) – When this bit is set, low AC line voltage will generate a fault.

Bit 1 (Ac High Volt) – When this bit is set, high AC line voltage will generate a fault.

Bit 2 (Ac Low Freq) – When this bit is set, low AC line frequency will generate a fault.

Bit 3 (Ac High Freq) – When this bit is set, high AC line frequency will generate a fault.

Bit 4 (High dFdt) – When this bit is set, high dF/dt will generate a fault.

Bit 5 (I Imbalance) – When this bit is set, high current imbalance will generate a fault.

Bit 6 (V Imbalance) – When this bit is set, high voltage imbalance will generate a fault.

Bit 7 (PWM SyncLost) – When this bit is set, loss of PWM synchronization will generate a fault.

Bit 8 (Inverter Flt) – When this bit is set, a fault in the Inverter will fault the Converter.

239

[Fault Clear]

Resets faults and clears the fault queue.

“Ready” = A new value may be entered.

“Clear Faults” = A fault is reset.

“Clr Fault Que” = The fault queue is cleared.

Default:

Options:

0

0
1
2

“Ready”

“Ready”
“Clear Faults”
“Clr Fault Que”

242

[Power Up Marker]

Displays the elapsed time at power up. This is used to know if a fault occurred since the
last time power was applied.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hrs

243

[Fault 1 Code]

Displays the most recent fault code detected.

Default:

Min/Max:
Units:

Read Only

0/65535
0

244

[Fault 1 Time]

Displays the time stamp for the most recent fault detected.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hrs

245

[Fault 2 Code]

Displays the most second recent fault code detected.

Default:

Min/Max:
Units:

Read Only

0/65535
0

246

[Fault 2 Time]

Displays the time stamp for the most second recent fault detected.

Default:

Min/Max:
Units:

Read Only

0.0000/429496.7295
0.0001 Hrs

Fil

e

Gr

oup No.

Parameter Name & Description

Values

Bit
Definition

In

ve

rt

er

Flt

PWM Syn

cLos

t

V I

m

balanc

e

I Imba

la

nce

High

dF

dt

Ac

High

F

req

A

c Low

F

re

q

Ac

High

V

olt

A

c Low

V

olt

Default

x

x

x

x

x

x

x

1

0

1

1

0

1

1

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled
x = Reserved